What conductor size will an LC1D115 or LC1D150 accept?

Product Line:
 
Tesys D line Contactors
 
Resolution:
 
With the LA9D11560* terminal:

Using (1) Conductor:
Stranded Cable without cable end; #8 to 250 MCM.
Stranded Cable with cable end; Not recommended.
Solid Cable without cable end; #8 to 250 MCM.


Using (2) Conductors: (will accept one of each size listed below)
Stranded Cable without cable end; #8 to 250 MCM and #8 to #1
Stranded Cable with cable end; Not recommended.
Solid Cable without cable end; #8 to 250 MCM and #8 to #0.



CTA-ID : 2006178