Technical FAQs

Ask a Question

What quantity and size of conductors can be used on a 400SN neutral assembly?

Issue:
Product feature

Product Line:
CB Enclosure

Environment:
Product feature

Cause:
Clarification

Resolution:
The 400SN accepts (1) #1 AWG - 600 kcmil, or (2) #1/0 AWG - 250 kcmil aluminum or copper conductors, in and out. Two service grounding lugs each accepts (1) #4 AWG - 300 kcmil aluminum or copper conductor.


CTA-ID : 2007284
Was this helpful?
What can we do to improve the information ?