Technical FAQs

Ask a Question

How many lugs can be put on a Powerpact R breaker?

Product Line:
Circuit Breakers

Environment:
Electrical Distribution Equipment

Resolution:
The RLTB terminal pad kit can handle 8 lugs per connection. They must be installed in pairs. Lug kit # AL2500RK.
Wire range is 1/0 AWG to 750 kcmil.
 
Was this helpful?
What can we do to improve the information ?