ILINE Panelboard Terminal Data

Issue:
ILINE  Panelboard Terminal Data

Product Line:
ILINE Panelboard

Environment:
New and existing ILINE Panelboards

Cause:
Need to select wire for installation or check the terminal data to mean existing wire onsite

Resolution:
Below is the terminal data for all of the panelboards found on page 9-40 in Digest 176, Section 9. Table 9.187 shows the terminal data for the phase and neutral lugs on main lug panels. Table 9.188 shows the standard terminal for main breaker available for ILINE panelboard (please see page 7-41 of Digest 176, Section 7 or page 3-28 of the Supplemental Digest 176, Section 3 for other terminal options for given breakers).

Standard Mechanical Lugs—Main Lugs
Amp Lug Wire Range Wire Range Wire Bendind Space per NEC Table 373-6
225 A one #6–300 kcmil Al or Cu one #6–300 kcmil Al or Cu
400 A two #2–600 kcmil Al or Cu one #2–600 kcmil Al or Cu
600 A two #2–600 kcmil Al or Cu two #2–500 kcmil Al or Cu
800 A (4) 3/0–750 kcmil Al or Cu (3) 3/0–500 kcmil Al or Cu
1200 A (4) 3/0–750 kcmil Al or Cu (4) 3/0–500 kcmil Al or Cu


Standard Mechanical Lugs—Main Circuit Breaker

Amp Circuit Breaker Type Lug Wire Range Wire Range Wire Bendind Space per NEC Table 373-6
100 A FA, FH, FI one #14-1/0 Al or Cu one #14-1/0 Al or Cu
150 A HD, HG, HJ, HL one #14-3/0 Al or Cu one #14-3/0 Al or Cu
225 A KI one #4-300 kcmil Al or Cu one #4-300 kcmil Al or Cu
250 A JD, JG, JJ, JL one #1/0-#4/0 Al or Cu one #1/0-300 kcmil Al or Cu
LX, LXI, LE two #1-350 kcmil Al or Cu two #1-350 kcmil Al or Cu
400 A LA, LH one #1-600 or two #1-250 kcmil Al or Cu one #1-600 kcmil Al or Cu
600 A LC, LI, LX, LXI, LE two 4/0-500kcmil Al or Cu two 4/0-500kcmil Al or Cu
800 A MG, MJ, PG, PJ, PL three 3/0-500 kcmil Al or Cu three 3/0-500 kcmil Al or Cu
1200 A PG, PJ, PL, RGC, RJC, RLC four 3/0-500 kcmil Al or Cu four 3/0-500 kcmil Al or Cu

CTA-ID : 2016310