Technical FAQs

Ask a Question

What is the consumption of the control coil for 8502SD contactor?

For 2 & 3 pole devices 311 VA inrush and 37 VA sealed for 60 hertz or 296 VA inrush and 36 VA sealed for 50 hertz. For & 5 pole devices 438 VA inrush and 38 VA sealed for 60 hertz or 429 VA inrush and 37 VA sealed for 50 hertz.

This also applies to all 8536SD, 8538SD, 8539SD, 8606SD, 8630SD, 8640SD, 8702SD, 8736SD, 8738SD, 8739SD, 8810SD, 8903SP, 8940 Size 2 except ``NP``, 8941ND, 8941CD, 8941UD, and 8941DD devices.


CTA-ID : 4789
Was this helpful?
What can we do to improve the information ?