Technical FAQs

Ask a Question

What are the part#s and specifications for field installable shunt trip accessory for MG, MJ, PG, PJ, PL, RG, RJ, RL Powerpact breakers?

Issue:
What are the part#s and specifications for field installable shunt trip accessory for MG, MJ,PG, PJ, PL, RG, RJ, RL Powerpact breakers?

Product Line:
Powerpact M, P and R frame

Environment:

Cause:

Resolution:
Operating Threshold 0.7 to 1.1 Vn for shunt trip,  0.85 to 1.1 Vn for closing coil (closing coil for electrically operated P frame only)
Power Consumption (VA or W) Steady-State/Inrush 4.5/200 VA
Shunt trip (MX1) and shunt close (XF) circuits must be energized for minimum of 200 ms.
Circuit Breaker Response Time at Vn
50 ms ±10 for shunt trip
55 ms for closing coil (electrically operated P frame only)

S33658 for 12Vdc
S33659 for 24/30Vac/dc
S33660 for 48/60Vac/dc
S33661 for 100/130Vac/dc
S33662 for 200/250Vac/dc
S33663 for 277Vac
S33664 for 380/480Vac


CTA-ID : 2021023
Was this helpful?
What can we do to improve the information ?