Technical FAQs

Ask a Question

What is the standard terminal lug wire size for the QMB225W, QMB325W and QMB365W fusible switches?

Issue:
product design features

Product Line:
QMB branch switches

Environment:
Terminal lug data

Cause:
Application

Resolution:
Each pole of these switches contains 2 lugs and each lug will accept (1) 3/0 - 600kcmil Al/Cu wire, Therefore the switch will accept (2) #3/0 - 600 kcmil Al/Cu wire per phase(or per pole).


CTA-ID : 2026822
Was this helpful?