Technical FAQs

Ask a Question

Is there a GFI option for the breakers used in the NF panelboards? (EDB, EGB, EJB)

Issue:
Is there a GFI option for the breakers used in the NF panelboards? (EDB, EGB, EJB)

Product Line:
NF Panelboards, E Frame Circuit Breaker

Environment:
Products in North America

Cause:
Need ground fault protection for a circuit in a NF panelboards.

Resolution:
The EDB, EGB, and EJB circuit breakers do not come with a GFI option for people protection at levels 4 – 6 mA. They are available with equipment ground-fault protection at 30mA (EPD).
 
  18 ka @480Y/277 Vac 35 ka @480Y/277 Vac 65 ka @480Y/277 Vac
10 A EDB14010EPD EGB14010EPD EJB14010EPD
20 A EDB14020EPD EGB14020EPD EJB14020EPD
30 A EDB14030EPD EGB14030EPD EJB14030EPD
40 A EDB14040EPD EGB14040EPD EJB14040EPD
50 A EDB14050EPD EGB14050EPD EJB14050EPD