Is the communicating shunt trip and close coil for the Masterpact continuous-duty or momentary?

Issue:
Is the communicating shunt trip and close coil for the Masterpact continuous-duty or momentary?

Product Line:
Masterpact, Powerpact

Environment:

Cause:

Resolution:
Voltage may be applied continuously.  When hard wired (not useing modbus to operate) the plunger will only extend for 0.5 seconds and then retract.  When using modbus to operate the coil,  the plunger will stay extended as long as voltage is applied to the terminals.
With the noncommunicating device the plunger will stay extended as long as voltage is applied to the terminals.