What is the lug data for PowerPact Q frame breakers such as QB, QD, QG, QJ?

Issue:
What is the lug data for PowerPact Q frame breakers such as QB, QD, QG, QJ?

Product Line:
PowerPact Q frame Breakers

Environment:
This applies to all PowerPact Q frame breakers Unit mount and I-Line.

Cause:
Can the lugs on a PowerPact Q frame breaker be replaced or changed out to a different size? 

Resolution:
Replacement lugs are not available for PowerPact Q-frame circuit breakers. The lug mounting screw on PowerPact Q frame breakers is sealed preventing the removal of the lug. When studs are installed they also can not be removed or replaced with lugs as the stud mounting screw is blocked preventing it from being removed. Lugs for the PowerPact Q-frame circuit breakers accept (1) #4 AWG to 300 kcmil Al or Cu conductors, except for the 250A breaker which are suitable for copper conductors only.


CTA-ID : 2034865
Was this helpful?
What can we do to improve the information ?