What is the catalog number for a sensor plug for a Powerpact or Masterpact breaker? Installation notes provided.

Product Line:
Circuit Breakers

Environment:
Applies to Powerpact P and R, Masterpact NW and NT

Resolutions:

Note: See bottom of list for Y frame (6p) Masterpact replacement sensor plugs.

Rating (A)                       Catalog Number

100*                               S47051 *Cannot be installed into a circuit breaker with original sensor plug higher than 250 A. Likewise a circuit breaker with original
250*                               S47052 sensor plug of 100 A or 250 A cannot be replaced with a sensor plug higher than 250 A.
400                                 S47053
600                                 S48823
630                                 S33091
800                                 S33092
1000                               S33093
1200                               S48824
1250                               S33094
1600                               S33095
2000                               S33982
2500                               S33983
3000                               S48825
3200                               S33984
4000                               IEC S47820
4000                               S47824
5000                               S47825
6000                               S48827
6300                               S47826

*Cannot be installed into a circuit breaker with original sensor plug higher
than 250 A. Likewise a circuit breaker with original sensor plug of 100 A or
250 A cannot be replaced with a sensor plug higher than 250 A.

*Special Y frame sensor plugs:

Rating (A)                     Catalog Number

2000                              S47821
2500                              S47822
3000                              S48826
3200                              S47823


Installation notes:
Masterpact NT and NW:  sensor plugs are field installable down to 50% of the FRAME  rating.   Example:  A Masterpact with a 1600 amp frame can receive sensor plugs from 800-1600 amps.

Powerpact P and R:  sensor plugs are field installable down to 50% of the CURRENT rating.  Example:  A Powerpact P frame breaker with 800 amp sensor installed at the factory can only receive sensors from 400-800 amps.  You can't go higher than what was originally installed at the factory.

For complete details on installing sensor plugs and their restrictions, please see attached instruction bulletin  48049-145-03.