Technical FAQs

Ask a Question

Aux contact - when does it operate?; Alarm switch - when does it operate?

The `A` aux contact will always follow the breaker contact, whether tripped or just turned on or off. The `B` contact is opposit the breaker contacts.
The `A` alarm contact will close when the breaker trips. The `B` contact will close when the breaker is reset.


CTA-ID : 2044828
Was this helpful?