What is each terminal wire range and the torque required, for the PK3GTA through PK23GTA,Ground Bars used in QO and Homeline load centers?

Issue:
Product features

Product Line:
Load Center Ground Bars

Environment:
Wire range

Cause:
Wire installation

Resolution:
The terminals provided on the PK3GTA through PK23GTA ground bars will accept the following:
Wire Sizes: 
(1) #14 - #4 CU / AL  
(2) #14 CU wires
(2) # 12 CU / AL wires
(2) #10 AL wires 

Torque requirements:
Wire range                             Torque LB-IN
(1) #4 CU / AL                            35
(1) #6 CU / AL                            35
(1) #8 CU / AL                            25
(1) #10 - 14 CU, #10 - 12 AL        20 
(2) #14 CU                                 25
(2) #12 CU / AL                          25
(2) #10 AL                                  25

SEE THE ATTACHMENT FOR THE DIMENSIONAL INFORMATION FOR THE GROUND BARS.