What is the size of the transition section from 5/15kV Outdoor NEMA 3R HVL switchgear to Masterclad metal clad switchgear?

The transition is done in the rear of the HVL switch. The HVL enclosure is extended to be 80" deep. A 3" collar is used between the HVL section and the metal clad section. These units are front aligned. It can also be done with a 22" wide transition and a 3" collar.