What are the torque requirements for QO wire binding screws and clamp plates?

Issue:
What are the torque requirements for QO / QOB wire binding screws and clamp plates?

Product Line:
QO Load Centers/NQ Panelboards

Environment:
Maintenance

Cause:
Installation/PMO

Resolution:
Scroll down for complete information.
QO/QOB 10A - 30A, 1,2 and 3-pole, all interruption ratings: 36 lb.-in.
QO/QOB 35 - 70A, 2 pole and 40 - 60A 3-pole, 10kA: 45 lb.-in.
QO/QOB-VH, QOH 40 - 125A, 2-pole, 22kA & 42kA: 50 lb.-in.
QO/QOB-VH, 40 - 100A, 3-pole, 22kA: 50 in.-lb.
QO/QOB, 70 - 100A, 3-pole, 10kA: 50 lb.-in.
QO/QOB-H, 40 - 100A, 2-pole 240Vac: 50 lb.-in.
QO/QOB, 80 - 125A, 2-pole, 10kA: 50 lb.-in.
QO Tandem (Ex: QO2020, QO1515...): 25 lb.-in.










CTA-ID : 2051202
Was this helpful?