Technical FAQs

Ask a Question

What is the wire range for the sub-feed lug kits, NQSFL1 , NQSFL2 and NQSFL4 ?

Issue:
What is the wire range for the sub-feed kits, NQSFL1, NQSFL2 and NQSFL4?

Product Line:
NQ panelboards and accessories

Environment:
Installation 

Cause:
Determination of conductor size for specific sub-feed lug kits.

Resolution:
The below table shows the terminal data for the incoming and outgoing wires. See instruction bulletin, 80043-729-01 or 80043-745-01
 
Amp Catalog # Incoming Outgoing
100 NQSFL1 one #6-2/0 Al or Cu one #6-2/0 Al or Cu
225 NQSFL2 one 1/0-350 kcmil Al or Cu one 1/0-350 kcmil Al or Cu
400 NQSFL4 one 1/0-750 kcmil Cu only one 1/0-750 kcmil Cu only


CTA-ID : 2052395
Was this helpful?
What can we do to improve the information ?