Can the PowerPact H and J breakers be used on a Corner grounded delta system?

Issue:
Can the PowerPact H and J breakers be used on a Corner grounded delta system?

Product Line:
PowerPact H and J Moled Case Circuit Breakers

Environment:
Does this apply to 240Vac and 480Vac corner grounded systems?

Cause:
How are the breakers used on these systems?

Resolution:
Yes, the PowerPact H  and J can be used on both 3 phase 240 and 480v grounded B phase systems.
Only 2P breakers are listed for use on 240Vac corner grounded systems.  Only 3P breakers are listed for use on 480Vac corner grounded systems.
See the attached file: corner grounded.xlsx