Can an NF panel Series E1 with a Factory installed 400 amp LAL36400 Main breaker, be converted to a Main lug panel?

Issue:
Can an  NF panel Series E1 with a Factory installed 400 amp LAL36400 Main breaker, be converted to a Main lug panel?

Product Line:
NF Panelboard

Environment:
Application

Cause:
Field Changes

Resolution:
The main breaker kit should remain in place so the panel will utilize the same box and trim. The following parts will be required per panel:
(1) 80113-270-50 Barrier Assembly
(1) NFALM4 Main Lug Kit
(1) 80103-079-02 Closing Plate
(4) 21593-17080 Screws
NOTE: THIS DOES NOT INCLUDE INTERIORS SUPPLIED W/ AN LC MAIN BREAKER.

Revision 11/2015:
Part number 80113-270-50 is now obsolete with no replacement.  Consider a local metal fabricator custom make something to replace it. 




CTA-ID : 2017333