Technical FAQs

Ask a Question

What enclosure size do we recommend for the new Powerpact L frame breakers ?

Recommended minimum dimensions for both standard 80% and 100% ratings are:
For LD, LG, LJ, and LL Breakers:
(h x w x d)
35.48 x 12.00 x 4.45 in.
(901 x 305 x 113 mm)

For LR Breakers:
(h x w x d)
40.5 x 13.75 x 4.33 in.
(1030 x 350 x 110 mm)