ATV212 with the optional VW3A1101 keypad is showing connection in progress on power up.

Issue:
ATV212 with the optional VW3A1101 keypad is showing connection in progress on power up.

Product Line:
Altivar 212

Environment:
All 

Cause:
Display will not come up you will need to check the baud rate and parity settings. 

Resolution:
Verify the following parameters:
F800=1 (Baud rate) 1= 19.2K
F801=1 (Parity) 1= Even parity
F802=1 (Address)
Also, the keypad Flash must be V1.1IE29 or higher.  