Technical FAQs

Ask a Question

ATS48 basic programming

Issue:
ATS48: Basic programming

Product line:
Altistart ATS48

Environment:
All models, all serial numbers

Cause:
Basic programming set up for the ATS48 soft starters.

Resolution:
Set menu Parameter

IN= FLA motor amps
ACC= acceleration
DEC= deceleration
ILT=current limit 400%  or 4X your motor current is default value.

DRC menu CLP= Off (Torque Control)
Ref ATS48 programming manual S1A37491
Was this helpful?
What can we do to improve the information ?