Technical FAQs

Ask a Question

What is the replacement for an FAL Mag-Gard MCP (motor circuit protector)?

Product Line:
Legacy motor circuit protector

Resolution:
The replacement is in the following table. 
Note that the dimensions are different and the replacement may not fit properly in the original equipment

 

 

Breaker Amps Trip Range Replacement Trip Range
FAL3600311M  3 8-28 HJL36030M71 9-325
FAL3600712M  7 18-70 HJL36030M71 9-325
FAL3601513M  15 50-180  HJL36030M71 9-325
FAL3603013M  30 50-180  HJL36030M71 9-325
FAL3603015M  30 100-350  HJL36030M71 9-325
FAL3605014M  50 75-260  HJL36050M72 84–546
FAL3605016M  50 150-580  HJL36050M72 84–546
FAL3610016M  100 150-580  HJL36100M73 180–1040
FAL3610018M  100 300-1100  HJL36100M73 180–1040
FAL3615024M  150 450-1100  HJL36150M74 348–1690
 
Breaker Amps Trip Range Replacement Trip Range
FHL3600311M  3 8-28 HJL36030M71 9-325
FHL3600712M  7 18-70 HJL36030M71 9-325
FHL3601513M  15 50-180  HJL36030M71 9-325
FHL3603013M  30 50-180  HJL36030M71 9-325
FHL3603015M  30 100-350  HJL36030M71 9-325
FHL3605014M  50 75-260  HJL36050M72 84–546
FHL3605016M  50 150-580  HJL36050M72 84–546
FHL3610016M  100 150-580  HJL36100M73 180–1040
FHL3610018M  100 300-1100  HJL36100M73 180–1040
FHL3615024M  150 450-1100  HJL36150M74 348–1690