Technical FAQs

Ask a Question

What is the replacement for an FAL Mag-Gard MCP (motor circuit protector)?

Product Line:
Legacy motor circuit protector

Resolution:
*****Note: Dimensions are different and the replacements listed below may not fit properly in the original equipment.
You will need to verify the type of equipment the original breaker is installed in before ordering. *****


The replacement is in the following table. 


 

 

Breaker Amps Trip Range Replacement Trip Range
FAL3600311M 3 8-28 HJL36030M71 9-325
FAL3600712M 7 18-70 HJL36030M71 9-325
FAL3601513M 15 50-180 HJL36030M71 9-325
FAL3603013M 30 50-180 HJL36030M71 9-325
FAL3603015M 30 100-350 HJL36030M71 9-325
FAL3605014M 50 75-260 HJL36050M72 84–546
FAL3605016M 50 150-580 HJL36050M72 84–546
FAL3610016M 100 150-580 HJL36100M73 180–1040
FAL3610018M 100 300-1100 HJL36100M73 180–1040
FAL3615024M 150 450-1100 HJL36150M74 348–1690
 
Breaker Amps Trip Range Replacement Trip Range
FHL3600311M 3 8-28 HJL36030M71 9-325
FHL3600712M 7 18-70 HJL36030M71 9-325
FHL3601513M 15 50-180 HJL36030M71 9-325
FHL3603013M 30 50-180 HJL36030M71 9-325
FHL3603015M 30 100-350 HJL36030M71 9-325
FHL3605014M 50 75-260 HJL36050M72 84–546
FHL3605016M 50 150-580 HJL36050M72 84–546
FHL3610016M 100 150-580 HJL36100M73 180–1040
FHL3610018M 100 300-1100 HJL36100M73 180–1040
FHL3615024M 150 450-1100 HJL36150M74 348–1690
Was this helpful?
What can we do to improve the information ?