Technical FAQs

Ask a Question

What is the current draw for a Micrologic 5 and 6 trip units for Powerpact H, J, L breakers?

Issue:
How much current is required to energize Micrologic 5.2, 5.3, 6.2, 6.3 trip units for Powerpact H, J, and L breakers?

Product Line:
Powerpact H, Powerpact J, Powerpact L circuit breakers

Environment:
Electrical distribution systems

Cause:
It is necessary to adequately size control power transformers for the load they will serve

Resolution:
Each Micrologic 5.2, 5.3, 6.2, 6.3 trip unit requires a 24 Vdc supply capable of delivering 30 mA.
Was this helpful?
What can we do to improve the information ?