Technical FAQs

Ask a Question

What is the wait time to reset SnbF on an ATS22?

Issue:
When the ATS22 trips on SnbF, the fault does not reset immediately. 

Product Line:
ATS22

Environment:
All models and frame sizes

Cause:
The number of starts set by Snb and SLG has been exceeded.

Resolution:
The wait time depends on the frame size.  The control power must be on to run the timer.
Frame size A is 5 minutes.
Frame size B, C, D and E is 15 minutes.
Was this helpful?
What can we do to improve the information ?