R2 can not be changed in the I/O Menu on the ATV61 and ATV71 drives?

Issue:
ATV61 can not change R2 assignment ?

Product Line:
ATV61 ATV71 Altivar

Environment:
All

Cause:
Programming change for R2 relay

Resolution:
Check to verify no run command being commanded or the drive is in RDY state.
Check menu 1.7 application menu see if the (OCC) output contactor command is not assigned to R2.