What causes an OL2 fault on the ATV21 and ATV212 drives?

Issue:
What causes an OL2 fault on the ATV21 and ATV212 drives?

Product Line:
Altivar ATV21 and ATV212

Environment:
All

Cause:
Motor Overload

Resolution:
OL2 indicates the drive is detecting a Motor Overload fault.
This will happen when the motor current exceeds the level programmed in the tHr parameter (works the same as a motor overload relay on a motor starter).
High current can be caused by:
Excessive load applied to the motor (motor is too small for the load).
Motor is jammed or stuck (locked rotor condition).
Motor is running a low speed for a long time (reduces the cooling of the fan on the motor).
Incorrect setting of the Pt (Motor Control Mode) parameter.
 