How are the ATS48 soft starters configured for a deceleration ramp instead of freewheel stop?

ISSUE:
How are the ATS48 soft starters configured for a deceleration ramp instead of freewheel stop?

Product Line:
ATS48 series soft starters.

Environment:
All makes, All models

Cause:
Customer needs a ramp stop to allow a check valve to close slowly to prevent water hammering.

Resolution:
Under the Settings Menu (Set) set parameter STY to D to select a deceleration stop type.
Under the Settings Menu (Set) set parameter DEC to the time, in seconds, that you want the starter to take to bring the motor to a stop after the run command is removed.