ATV32 Devicenet setup configuration assistance.

Issue:
ATV32 Devicenet setup configuration assistance.

Product Line:
Altivar 32

Environment:
All ATV32 drives with Devicenet option card VW3A3609.

Cause:
Programming assistance

Resolution:
CONF enter
FULL enter
CON enter
CbD enter

Communcations settings

AdrC= address= set 0-63
bdr= Bit rate=  Auto, 125K 250K,500K  choose one
bdrU= Data rate= Auto, 125K, 250K, 500K choose one
C1DA= Assembley set up= 20, 21, 100, unconfig  choose one
OCA1 and OMA1 are for assemblies 100 and 101 only.

See page 20 of 88 in the attached manual.
 

Was this helpful?
What can we do to improve the information ?