Is the L600AWK suitable for use with the 4 Pole L Frame PowerPact Circuit Breaker?

Issue:
Application

Product Line:
Circuit Breaker Enclosure

Environment:
Selection

Cause:
Selection

Resolution:
No, only 3 Pole circuit breakers can be used.
NOTE: The L600AWK will not accept the L Frame PowerPact breaker with the LSIG function due to no Neutral CT capability.