Technical FAQs

Ask a Question

What size cable can fit in the AL600LS52K3 lugs ?

Issue:
Conductor size in Powerpact L lugs

Product Line:
Molded Case Circuit Breakers

Environment:
Powerpact LCL

Cause:
Fit

Resolution:
The lugs can accomodate 2 - 2/0 - 500kcmil  Al or CU including the following standard wire sizes:
2/0 3/0 4/0 250 300 350 400 500

Was this helpful?
What can we do to improve the information ?