When attaching a PA,PH,PC,PX or PE breaker to bus bars, what torque is required for the 24 carriage bolts?

Product Line:
PA, PH, PC, PX and PE Circuit Breakers

Products sold and installed in the USA and Canada

There are 24 carriage bolts used to attach the above breakers to bus bars (4 bolts per pole, line and load).
The proper torque is 240 lb-in (27 N-m).
See below drawing as a reference (from bulletins 48040-189-06 and 48040-940-03).