What voltage level causes an Overvoltage Fault (OSF) on an ATV61 or ATV71 series drive?

Issue:
What voltage level causes an Overvoltage Fault (OSF) on an ATV61 or ATV71 series drive?

Product Line:
Altivar 61 and Altivar 71 series drives.

Environment:
All part numbers ending with M3XXX or N4XXX,  All serial numbers.

Cause:
Customer needs to know the voltage that causes this fault to occur.

Resolution:
- The over supply flag OSF FAULT is set when the drive is in the capacitor charging state and the dc bus voltage is higher than OSFH_Level.
- The over supply flag OSF FAULT is set when the drive is in the PWM disabled state and when the dc bus voltage is higher than OBFH_Level.
- The flag OSF FAULT is reset when the dc bus voltage is lower than OSFL Level.
- The over supply detection is always activated and cannot be inhibited.


 