What is the tripping current for a Multi 9 GFP Ground Fault Protector?

PRODUCT LINE:
Multi 9 C60 Ground Fault Protectors

RESOLUTION:
Tripping currents are as follows:
GFP30     Must trip at 29.9 mA; must not trip below 22.1 mA      
GFP100     Must trip at 98.9 mA; must not trip below 73.1 mA      
GFP300     Must trip at 299 mA; must not trip below 221 mA      
 