ISSUE
Maximum load of e-frame breaker accessories

PRODUCT LINE
E-frame Breakers/NF Panels

ENVIRONMENT
E-frame accessories

CAUSE
Needing to know how much the accessory can take

KEY WORDS
e-frame edb egb ejb nf panelboard panel accessory accessories aux switch auxiliary bell alarm NO 1a 1b shunt trip maximum load coil burden

RESOLUTION
Auxiliary Switch: Maximum load of 10 A at 120 Vac, 50/60 Hz
Alarm Switch: Maximum load of 7 A at 120 Vac, 50/60 Hz
Shunt Trip: Coil burden of 288 VA
 