Technical FAQs

Ask a Question

Are power factor correction capacitors recommended with Altivar Variable Frequency drives?

Issue:
Power Factor correction capacitors

Product Line:
Altivar

Environment:
All models and serial numbers

Cause:
None

Resolution:
Schneider Electric does not recommend using power factor correction capacitors with variable frequency drives.  Capacitor banks in distribution systems with 6 pulse variable frequency drives may result in undesirable resonant currents.
Was this helpful?
What can we do to improve the information ?