Technical FAQs

Ask a Question

Can the 9065 type SF solid state overload relays mount to an 8536 type S starter?

 

Issue: Can the 9065 type SF solid state overload relays mount to an 8536 type S starter?


Product Line:
All Schneider Electric products

Environment:
Products sold and used in the United States

Cause: Can the 9065 type SF solid state overload relays mount to an 8536 type S starter?

 
Resolution: The solid state overload relays from size 00 to size 1 are the same for separate mounting and replacement/retrofit mounting; size 2 and above use the type ST instead of the type SF and these devices are designed for separate mounting, not for mounting to a starter. The 9065 type ST should be used to mount to size 2 and above starters.

 

Keywords: separate mounting, solid state overload relay, SSOLR, retrofit, direct mount, replacement

 

 


 
Was this helpful?
What can we do to improve the information ?