Technical FAQs

Ask a Question

What is the output voltage from the ATV212 RYA-RYC contact?

Issue:
ATV212 drive running status

Product Line:
Altivar 212 ATV212 

Environment:
All
 
Cause:
Status indication feedback

Resolution:
There is no drive output voltage from the RYA-RYC contact.  This is a dry contact.

Specs are as follows:
Minimum switching capacity: 3mA for 24Vdc
Maximum switching capacity:
   resistive load 3A for 250Vac or 30Vdc
   inductive load 2A for 250Vac or 30Vdc
Maximum response time: 7msec +- 0.5msec
Was this helpful?
What can we do to improve the information ?