What is the maximum amperage that can be fed into the SR69064A Solar Ready Kit used with certain CSED panels?

Issue:
Application

Product Line:
CSED

Environment:
Application

Cause:
Verification

Resolution:
The installing electrical contractor should consult the latest National Electrical Code (NFPA 70) that is being enforced in the installation area.
However, the lugs provided in the SR69064A provides for a maximum #2/0 AWG AL or CU conductor. Based on 75 Degree C conductor ampacity, #2/0 AL is rated 135 ampere and #2/0 CU is rated 175 ampere. 