What is the coil burden for a 120V coil on a 8910DPA Series C definite purpose contactor?

Issue:
What is the inrush and sealed VA for 120V coil on a 8910DPA Series C definte purpose contactor?

Product Line:
Contactor

Environment:
Control Product

Cause:
Series C coil specifications for the 8910DPA 2P and 3P Defintie Purpose Contactor

Resolution:
The 120V coil(V02) for the 8910DPA is 6.5VA 60Hz sealed and 53VA 60HZ inrush.
See attachment for specification sheet including contact data and coil data.