Can the HRL or JRL circuit breaker be installed in the J250F, J250S, J250DS, J250SS, J250AWK or J250R circuit breaker enclosure?

Issue:
Application

Product Line:
CB Enclosures

Environment:
Application

Cause:
Verification

Resolution:
The J250 family of enclosures will accept only the HDL, HGL, HJL, HLL or JDL, JGL, JJL or JLL circuit breakers. The enclosures are not listed for use with the HRL or JRL circuit breakers.

We do have minimum recommended enclosure dimensions for them:

HRL:
80%: 18.13 x 8.63 x 4.13 in.
100%: 62 x 22.5 x 14 in.

JRL:
80%: 28.5 x 12.38 x 5.38 in.
100%: 62 x 22.5 x 14 in.