How to start an ATV312 drive using modbus for command?

How to start an ATV312 using Modbus?

Product Line:
Variable Frequency Drives

Applies to ATV312

Customer is not able to start the drive using Modbus.

Suggested to follow the status chart and send the values to the command word in sequence Hex 6 then 7 then F  to Address 8501 (assuming there is no offset)

Status Chart