Can I-Line busway be used for a single phase application ?

Issue:
Single Phase use of 3 phase product

Product Line:
Busway

Environment:
I-Line II

Cause:
Application

Resolution:
 
 
 
 

Yes, 3 pole feeder busway could be used and 2 poles/bars connected. If a neutral is required then 4w plug-in busway is required. The plug-in units, fusible or circuit breaker would only require 1 or 2 of the 3 poles to be used.