How can you program the ATV61 or ATV71 drive so that you can run the drive without the motor connected to it?

Issue:
How can you program the ATV61 or ATV71 drive so that you can run the drive without the motor connected to it?

Product Line:
Altivar ATV61 ATV71

Environment:
All

Cause:
Needs to test the drive to see if there is a problem with it wants to run the drive open circuit without the motor connected to it.

Resolution:
Go to menu 1.8 Fault management
Find Output Phase Loss
Set it to nO
Go to menu 1.6 Command
Find Motor Control Type and set to VF 2pts.

Note: make sure to set Ouput Phase Loss back to yes after testing is done.   Wear neccessary protective equipement while testing with OPL set to off, voltage and current will be available at the output terminals of drive
 