How do you program an auto/manual or com via logic input on the ATV630 process drive?

Issue:
How do you program an auto/manual or com via logic input on the ATV630 process drive?

Product Line:
Altivar ATV630 Process drive

Environment:
All

Cause:
Wants to be able to wire in an HOC or HOA for switching between hand  and network control

Resolution:
Ref switching via logic input for Auto/HMI manual control example
Menu 5 complete settings enter (ok)
scroll down
Menu 5.4 Command and Refere enter (ok)
Config Ref Freq 1  = AI2
REf 1 B channel Ref Freq via Rmt (means HMI)
Ref 1 B Switching= DI4
example DI4 is low Ref is AI2,  if DI4 is high then ref is HMI 
 
CMD switching via logic input for CMD channel 1 and CMD channel 2
Menu 5 complete settings enter (ok)
scroll down
Menu 5.4 Command and Refere enter (ok)
scroll down
Command switch= = DI4
Cmd channel 1 = terminals
Cmd channel 2 = HMI
example DI4 is low CMD is terminal, if DI4 is high then CMD is HMI

Control Mode= or CHCF you can find IO profile, separate or Not separate. 

 