What adjustments can be made to the ATS48 soft starter if the motor is stuck like on a grain elevator and it will not move?

Issue:
What adjustments can be made to the ATS48 soft starter if the motor is stuck like on a grain elevator and it will not move?

Product Line:
Altistart ATS48 soft starter

Environment:
All

Cause:
The grain elevator is loaded down and the motor is down.

Resolution:
If the motor is stuck or if they help breaking the load on start up try adjusting the following parameters.
DRC menu make sure your Torque control CLP is set to Yes.
SET menu set the t90 or Initial starting torque from 20% to 100% depending on what amount of torque is needed to start.
ILT= current limit try increasing 400% to 700%
tHP= Motor thermal protection set to class 20.

Once the motor breaks loose you can set all of the above parameters back to the original settings.

 
Was this helpful?