Can you land (3) 600 kcmil wire / per phase, to a HCP508612N panel ?


Issue:
Can (3) 600 kcmil wire per phase be terminated in a HCP508612N panel ?

Product Line:
I Line Panelboard

Environment:
Installation

Cause:
Cable size

Resolution:
Yes , (3) 600 kcmil can be landed to the Main lugs. This can be accomplished by removing the bottom endwall of enclosure box and ordering a HC4212DEX(S) surface, or (F) Flush, 12" box extension. This will allow the extra wire bending space, per NEC,  to land the (3) 600 kcmil wire/phase on the Main lugs which are able to provide for (4) 3/0-750kcmil/per phase wires.