On the ATV61 / ATV71 drives, why can the logic input assignments not be changed?

Issue:
On the ATV61 / ATV71 drives, why can the logic input assignments not be changed?

Product Line:
ATV61 ATV71

Environment:
All models

Cause:
Attempting to change LIx assignments in the menu 1.5 INPUTS/OUTPUTS

Resolution:
The logic input assignments in the 1.5 INPUTS/OUTPUTS menu are read only.  To change an assignment, go to the desired function and then assign that function to the logic input.