Can you scale the analog input for the ATV312 drives?

Issue:
Customer is looking to use a sensor that is 0-5V, or 1.8 to 2.3V for the analog input.

Product line:
ATV312, Altivar 312

Environment:
All

Cause:
Sensor output is not 0-10V, 0-20ma or 4-20mA.

Resolution:
The ATV312 only has a 0-10V scale for the analog input.  The only adjustment is for the current input on AI3 which is selectable as 0-20mA or 4-20mA.  Consider the ATV61, ATV71 drives if they need to scale the analog input signal to something other than 0-10V.