How do I disable the overload protection on an ATV312?

Issue:
External overloads are providing the protection.

Product Line:
ATV312

Environment:
All models and serial numbers

Cause:
None

Resolution:
You can disable the overload protection by setting parameter OLL [Overload fault mgt] to "nO" or "Ignore" in the FLt [Fault management] menu.