Do the ATV312 control wires need to be shielded?

Issue:
Do the ATV312 control wires need to be shielded?

Product Line:
Altivar 312

Environment:
All models

Cause:
Selecting control wire for potentiometer and logic inputs

Resolution:
The drive does not require shielded control wires.  Due to other nearby electrical circuits, it is recommended to use shielded twisted cables with a pitch of 25 - 50mm (1 - 2in), connecting the shielding to ground at each end.